Dual-chamber controlled air burner or dual- Room pyrolytic burner

Types of incineration design okay: Dual-chamber controlled air burner or dual – chamber pyrolytic incineration

Products of construction: The incineration shall have no type of asbestos, asbestos-containing chemicals, mercury thermometers, along with mercury switches. Refractory materials shall have the ability to meet pertinent criteria under ISO TC33 in addition to CEN/TC 187. Waste feed system right into the combustion chamber batch or constant loading: For continuous loading, the Automated billing ram or auger feed system shall be capable of infusing small amounts of waste in regular intervals and should have the ability to avoid waste from being fed when the burning chamber temperature is much less compared to 850 ° C. Additionally, the waste feed should just be able opened at or below 50 ° C in an ambient temperature degree of 21 ° C.Primary combustion chamber: Shall be constructed with a housing (reinforced to withstand interior pressures without deflection or harm to the refractory or other components ) supported with a structural construction and provided with refractory liner and insulation
Accessibility doors, openings, along with voids: All accessibility doors, openings, and also gaps shall be sealed to stop discharge of smoke in addition to exhaust gas and also to block admission of air through incineration operations. Doors subjected to fire or direct warm of combustion gases shall be lined using the Specific same type and also depth of refractory mobile liner and insulation as that utilized in the burning chamber

Grate method for your Main chamber Relocating grate, travel grate, reciprocating grate, or rotating drum grate

Main combustion chamber temperature degree # 850 ° C minus cool areas

Secondary combustion chamber: Shall be generated with an exterior casing (strengthened to endure internal stress without deflection or damages into the refractory or Several Other elements ) and provided with refractory insulation and lining

Secondary burning chamber temperature degree 1100 ° C or higher

Second burning chamber residence time # 2 seconds after the last shot of air in the next room