18 Electrical supply required 3-phase
19 Auxiliary fuel Diesel or paraffin
20 Main burner
21 Secondary (Later ) burner
22 Type of burners Automatic pressure jet
23 Output Primary Approx 600 000 kJ/hour
24 Output Secondary Approx 750 000kJ/hour
25 Emission control
Heated refractory screen
Low Speed grit arrester screen Constructed in
26 Paint Instance 400 Level Celsius resisting black
27 Paint stack 400 Level Celsius resisting aluminium
28 Temperature of case Not exceeding 90 degree Celsius
29 Intensifier
30 Automatic fan control
31 GRE Variable 1.5
32 Noise (primary)
Noise (secondary) 72 dBA
33 Transport and rigging of plant Such as crane Employ 76 dBA
34 Certification of Investigation as per Annexure 1
35 Commissioning of incineration
36 Guarantee 3 years
37 Training of operators
38 Availability of Neighborhood distributor for spare sparts
ANNEXURE 1
Common Name Chemical symbol Compliance: mg/Nm3 under Ordinary conditions of 10 Percent O2, 273 Kelvin and 101.3 kPa
Particulate matter 10
Carbon monoxide CO 50
Sulphur dioxide SO2 50
Oxides of nitrogen NOx expressed as NO2 200
Hydrogen chloride HCl 10
Hydrogen fluoride HF 1
Sum of Lead, arsenic, antimony, chromium, cobalt, copper, manganese, nickel, vanadium Pb+, As+, Sb+, Cr+, Co+, Cu+,
Mn+, Ni+, V 0.5
Mercury Hg 0.05
Cadmium Thallium Cd+Ti 0.05
Total organic compounds TOC 10
Ammonia NH3 10
Compliance: ng I TEQ/Nm3 under Ordinary conditions of 10 Percent O2, 273 Kelvin and 101.3 kPa