medical waste incinerators

All tags with text shall be in English.

 

 

 

 

Anti-Condensation Heaters

 

 

 

 

The Panel shall be provided with a thermostat controlled anti-condensation heater 240 V, 50 Hz.

 

 

 

 

Earthing System

 

All ordinary non-current carrying metal parts of the panel and related components shall be bonded to a frequent copper

earthbar conducting the entire length inside the switchboard.

 

The earthbar shall be located at the lower part of the framework work and provided with two termination points for

connection to the main earthing grid.

 

 

 

2.5      Ignition Oil Supply

 

 

MEDICAL WASTE INCINERATOR INTALI8ATION

Design, Supply, install, test and commission medical waste

Incinerator in Accordance with the attached specification. The cost shall

include all accessories such as the civil work and spare part

listing to make the system complete.

incineration burning capacity-250kg/hr                                                  NO       1

 

 

 

 

 

 

 

 

Jimma University Referal Hospital

Incinerator

Medical Waste Incinerator

Goal

For a complete destruction of waste from several hospital services from heat treatment of elevated fever in accordance

with EU standard on emission requirement

Waste from healthcare actions

Infections waste, laboratory cultures, waste kind performance room isolations material in contact with contaminated

patients, squander potentially being infected from pathogenic agents.

Pathological waste, individual fragments, bold, fetus, all body fluids, human cells.

Chemical waste laboratory reagents, disinfectants

Expired drugs.

Low radiation radioactive element. Medical waste incineration

Structure – CS plate cubes, FB reinforcement, caste refractory linings,

insulating material and    14 gage aluminum coat.

Sort of gasoline – Oil fired (Diesel)

Burning Ability – 250kg/hr and moisture around 80%

Duration-8-16/Constant

Average fuel consumption- Really little as much as possible

Control Form – PLC based performance

Operating Temperature- Primary chamber 800c± 50

– Secondary Chamber 1050c ± 50

Size of incineration — maybe not more than 15mx7.20m

Chimney — Q630x25meter elevation and 7mm thick CS.

Combustion efficiency — 99 percent

Mode of waste handling — Semi- Automatic via ram loader.

Mode of ash handling — Semi- automatic via grate and ash .

Pollution control equipment- Dry settlement zone

Doors — 1- waste charging doorway in main chamber

1-Clinker doorway in main chamber

1-Ash trolley access door in main chamber

1-Clean entrance door in secondary room

Burner -2- ignition burner in main chamber

2-after burner in secondary room.

Form – bundle mono block-fully automatic

Sort of burner performance – modulation control

Forced draught lover – 1- main air fan

1-secondary air lover

Gas storage tank- Capacity-2500liter over grond

– Material -6mm thick mild steel

-2-diesel pump, gate valve, sfety valve, strainer

pipe, pressure gage, check valve, control board

Level indicator. Etc

Refractory/insulation thickness- not less than 225mm

Ram loader capacity-0.75m3

Electrical provide -380v/3ph/50 Hz

End and painting type- powder coated

Audio/Visual alarm system- burner lockout, overload error

Electrical accessories — main and secondary room temperature

Controller /indicator, auto controllers, electrical

Control switches, push buttons, relays contavtors

Thermocouples, burner sequence controls,

Timers, emergency stop and alarms.

Ram loader capacity-0.75m3

Electrical supply -380v/3ph/50 Hz

Finish and painting type- powder coated

Audio/Visual alarm system- burner lockout, overload fault

Electrical accessories – primary and secondary chamber temperature

Controller /indicator, auto controls, electrical

Control switches, push buttons, relays contavtors

Thermocouples, burner sequence controllers,

Timers, emergency stop and alarms.