All tags with text shall be in English.
Anti-Condensation Heaters
The Panel shall be provided with a thermostat controlled anti-condensation heater 240 V, 50 Hz.
Earthing System
All ordinary non-current carrying metal parts of the panel and related components shall be bonded to a frequent copper
earthbar conducting the entire length inside the switchboard.
The earthbar shall be located at the lower part of the framework work and provided with two termination points for
connection to the main earthing grid.
2.5 Ignition Oil Supply
MEDICAL WASTE INCINERATOR INTALI8ATION
Design, Supply, install, test and commission medical waste
Incinerator in Accordance with the attached specification. The cost shall
include all accessories such as the civil work and spare part
listing to make the system complete.
incineration burning capacity-250kg/hr NO 1
Jimma University Referal Hospital
Incinerator
Medical Waste Incinerator
Goal
For a complete destruction of waste from several hospital services from heat treatment of elevated fever in accordance
with EU standard on emission requirement
Waste from healthcare actions
Infections waste, laboratory cultures, waste kind performance room isolations material in contact with contaminated
patients, squander potentially being infected from pathogenic agents.
Pathological waste, individual fragments, bold, fetus, all body fluids, human cells.
Chemical waste laboratory reagents, disinfectants
Expired drugs.
Low radiation radioactive element. Medical waste incineration
Structure – CS plate cubes, FB reinforcement, caste refractory linings,
insulating material and 14 gage aluminum coat.
Sort of gasoline – Oil fired (Diesel)
Burning Ability – 250kg/hr and moisture around 80%
Duration-8-16/Constant
Average fuel consumption- Really little as much as possible
Control Form – PLC based performance
Operating Temperature- Primary chamber 800c± 50
– Secondary Chamber 1050c ± 50
Size of incineration — maybe not more than 15mx7.20m
Chimney — Q630x25meter elevation and 7mm thick CS.
Combustion efficiency — 99 percent
Mode of waste handling — Semi- Automatic via ram loader.
Mode of ash handling — Semi- automatic via grate and ash .
Pollution control equipment- Dry settlement zone
Doors — 1- waste charging doorway in main chamber
1-Clinker doorway in main chamber
1-Ash trolley access door in main chamber
1-Clean entrance door in secondary room
Burner -2- ignition burner in main chamber
2-after burner in secondary room.
Form – bundle mono block-fully automatic
Sort of burner performance – modulation control
Forced draught lover – 1- main air fan
1-secondary air lover
Gas storage tank- Capacity-2500liter over grond
– Material -6mm thick mild steel
-2-diesel pump, gate valve, sfety valve, strainer
pipe, pressure gage, check valve, control board
Level indicator. Etc
Refractory/insulation thickness- not less than 225mm
Ram loader capacity-0.75m3
Electrical provide -380v/3ph/50 Hz
End and painting type- powder coated
Audio/Visual alarm system- burner lockout, overload error
Electrical accessories — main and secondary room temperature
Controller /indicator, auto controllers, electrical
Control switches, push buttons, relays contavtors
Thermocouples, burner sequence controls,
Timers, emergency stop and alarms.
Ram loader capacity-0.75m3
Electrical supply -380v/3ph/50 Hz
Finish and painting type- powder coated
Audio/Visual alarm system- burner lockout, overload fault
Electrical accessories – primary and secondary chamber temperature
Controller /indicator, auto controls, electrical
Control switches, push buttons, relays contavtors
Thermocouples, burner sequence controllers,
Timers, emergency stop and alarms.