DESCRIPTION OF WORKS The services and equipment described in this specification comprises the supply, delivery, installation, testing and commissioning of an incinerator and the associated accessories including oil installation at the Hospital. The tenderer is to ensure that the equipment they proposes to supply is from a reputable manufacturer with full spare back-up […]
Diesel incinerator. 25Kg/h. It will have mainly paper, cardboard and food, though also it will incinerate medical waste. So the incinerator shall be able to handle organic and hazardous waste. Spare parts for one year. The design should prevent any release of polluting substances into soil, surface water and groundwater. Combustion zone has to reach […]
Electrical safety: The medical waste incinerator shall meet the requirements of IEC 61010-2-040, UL 61010A-2-041, or an equivalent electrical safety standard; as weil as the electromagnetic compatibility requirements under EN 61326:1997 or equivalent standard. Physical: Safety Belts, pulleys, chains, gears and other rotating parts as well as sharp edges, located where persons come in close […]
Primary combustion chamber temperature # 850°C with no cold spots Secondary combustion chamber: Shall be constructed with an exterior casing (reinforced to withstand internal pressures without deflection or damage to the refractory or other components) and provided with refractory lining and insulation Secondary combustion chamber temperature 1100°C or higher Secondary combustion chamber residence time # […]
Materials of construction: The incinerator shall not have any asbestos, asbestos-containing substances, mercury thermometers, and mercury switches. Refractory materials shall be able to meet relevant standards under ISO TC33 and CEN/TC 187. Types of incinerator design acceptable: Dual-chamber controlled air incinerator or dual- chamber pyrolytic incinerator Waste feed system into the combustion chamber batch or […]